Hot Plug Rackmount UPS

CDH33-N Series UPS

  • The world’s highest density power solution (1.15 VA/cm3 or 18.81 VA/inch3)
  • 40kVA up to 1040kVA UPS capacity
  • Double Conversion with capability for switching to Multi-Mode
  • (Automatically switches between Double Conversion and Line Interactive modes according to mains status if Multi-Mode is activated)
  • Designed for standard 19” rack with 28 or 44 units height
  • Unlimited parallel expansion capability
  • 3-Level intelligent charging mode
  • Wide ranges of input voltage and input frequency
  • Excellent generator compatibility
  • 3-Phase input, 3-Phase output
  • Separated AC input of modules for rectifier and bypass
  • Hot plug/Hot swappable modular UPS
  • Capacity per module: 40kVA-36kW
  • Separated bypass for module
  • Shared or separated batteries in parallel configuration (selectable)
  • Selectable external battery quantity (384Vdc up to 480Vdc)
  • Adjustable charging current
  • Advanced battery management
  • Intelligent monitoring function for each module
  • Easy maintenance by providing MBB (Make Before Break) manual bypass for repairs and system support
  • Possibility of replacing any faulty module during operation, without affecting the other modules
  • Centralized monitoring unit for system
  • Optional Emergency Power Off function (EPO)
  • On-grid capability for testing UPS in 100% load without real full loads
  • Near zero MTTR (5min)

Technical Specifications

General

UPS Model CDH33-N40

XXXX are apparent power of UPS in kVA

XX up to 80, XXX up to 960, XXXX up to 1040

CDH33-N40, CDH33-N80, CDH33-N120, … , CDH33-N1040

Rated apparent power 40, 80, 120, 160, 200, 240, 280, 320, 360, 400, 440, 480, 520, 560,

600, 640, 680, 720, 760, 800, 840, 880, 920, 960, 1000, 1040 kVA

Applicable standard

IEC62040-3
UPS classification VFI SS CCC*

*C: 1 or 2 or 3 by order refer to IEC 62040-3

UPS topology

Double Conversion / Multi-Mode

(selectable by user)

Efficiency 96%

Parallel expansion capability

Unlimited
N+1 redundancy capability Yes
Dimensions and weight

CDH33-N40

CDH33-N80

CDH33-N120

CDH33-N160

CDH33-N200

CDH33-N240

CDH33-N280

CDH33-N320

CDH33-N360

CDH33-N400

CDH33-N440

CDH33-N480

CDH33-N520

CDH33-N560

CDH33-N600

CDH33-N640

CDH33-N680

CDH33-N720

CDH33-N760

CDH33-N800

CDH33-N840

CDH33-N880

CDH33-N920

CDH33-N960

CDH33-N1000

CDH33-N1040

Dimensions (H×W×D) Weight
1500 × 600 × 800 mm

1500 × 600 × 800 mm

1500 × 600 × 800 mm

1500 × 600 × 800 mm

2200 × 600 × 800 mm

2200 × 600 × 800 mm

2200 × 600 × 800 mm

2(2200 × 600 × 800) mm

2(2200 × 600 × 800) mm

2(2200 × 600 × 800) mm

2(2200 × 600 × 800) mm

2(2200 × 600 × 800) mm

2(2200 × 600 × 800) mm

2(2200 × 600 × 800) mm

2(2200 × 600 × 800) mm

3(2200 × 600 × 800) mm

3(2200 × 600 × 800) mm

3(2200 × 600 × 800) mm

3(2200 × 600 × 800) mm

3(2200 × 600 × 800) mm

3(2200 × 600 × 800) mm

3(2200 × 600 × 800) mm

3(2200 × 600 × 800) mm

3(2200 × 600 × 800) mm

3(2200 × 600 × 800) mm

3(2200 × 600 × 800) mm

210kg

260kg

310kg

380kg

530kg

590kg

640kg

940kg

1030kg

1090kg

1140kg

1190kg

1240kg

1300kg

1350kg

1650kg

1710kg

1760kg

1810kg

1870kg

1920kg

1970kg

2150kg

2200kg

2250kg

2310kg

Acoustic noise at 1m

≤58dBA
Degree of protection against hazards and water ingress IP20

Mean Time Between Failures (MTBF)

250,000h

Mean Time To Repair (MTTR)

5min

Environmental

Operating temperature

0°C to +40°C
Storage temperature -25°C to +55°C

Humidity

0 to 95% non-condensing
Altitude                                        at rated power

0.974 × rated power

0.920 × rated power

0.872 × rated power

0.820 × rated power

≤1500m

≤2000m

≤3000m

≤4000m

≤5000m

Input

Phases required

3Ph+N+PE
Rated voltage 400Vac

Voltage tolerance

100% load

70% load

50% load

 

±20%

-30% to +20%

-48% to +20%

Frequency range 35Hz to 70Hz

Power factor

≥0.99
THDi ≤3%

Bypass voltage range

max. voltage

min. voltage

 

400Vac +10%

400Vac -20% (optional -10%)

Output

Output phases available

3Ph+N+PE

Rated voltage

400Vac
Voltage regulation

double conversion mode

stored energy mode

 

±1%

±1%

Power factor

0.9
Frequency

double conversion mode

stored energy mode

 

50/60Hz ±10% (adj.)

50/60Hz ±0.1%

Crest factor

3:1
THD

linear load

nonlinear load

 

≤2%

≤3%

Transfer time

double conversion mode to stored energy mode

double conversion mode to bypass

 

0.00Sec

0.00Sec

Overload                           double conversion mode

up to110%

>110% up to 125%

>125% up to 150%

>150%

energy saving mode

 

60min

10min

1min

transfer to bypass

according to bypass breaker curve

Battery

Battery type

All types of lead acid and gel, sealed or non-sealed

Normal voltage

384Vdc up to 480Vdc (selectable)

Max. charge current per module

10A per module (10A per 40kVA power)

Protections

Short circuit

Overload

Output overvoltage

Overheat

Battery low

Battery reverse (optional)

Self-diagnostics

EPO

Display

UPS module

Audible & visual

Mains Failure, Low Battery, Overload, System Fault

Status LED & LCD

Double Conversion Mode, Energy Saving Mode, Low Battery,

Battery Test Failure, Overload, UPS Fault

LCD information

Input Voltage, Input Frequency, Output Voltage, Output Frequency,

Load Percentage, Battery Voltage, Parameters Set., History Record

UPS system

Central control

monitoring

UPS system information and control

Communication Interface

USB, RS485, Dry contacts (optional), SNMP card (optional), Relay card (optional), Parallel port