Tower

Features

  • 1, 2, 3, 6 and 10 kVA UPS capacity
  • Internal battery capability for 1,2 and 3kVA UPS
  • 1-Phase input, 1-Phase output
  • Double Conversion with capability for switching to Multi-Mode
  • (Automatically switches between Double Conversion and Line Interactive modes according to mains status if Multi-Mode is activated)
  • Intelligent controls with Digital Signal Processing (DSP)
  • Unlimited parallel expansion capability for 6 and 10 kVA UPS
  • 3-Level intelligent charging mode
  • Wide ranges of input voltage and input frequency
  • Excellent generator compatibility
  • Shared or separated batteries in parallel configuration (selectable)
  • Adjustable charging current
  • Advanced battery management
  • Intelligent monitoring function
  • Easy maintenance by providing optional MBB (Make Before Break) manual bypass
  • Optional Emergency Power Off function (EPO)

Technical Specifications

General

UPS Model CDT11‐N01/

CDT11‐N01i

CDT11‐N02/

CDT11‐N02i

CDT11‐N03/

CDT11‐N03i

CDT11‐N06 CDT11‐N10
Rated power 1kVA/0.8kW 2kVA/1.6kW 3kVA/2.4kW 6kVA/5.4kW 10kVA/9kW

Applicable standard

IEC62040-3
UPS classification VFI SS CCC*

*C: 1 or 2 or 3 by order refer to IEC 62040-3

UPS topology

Double Conversion / Multi-Mode

(selectable by user)

Efficiency 87% 89% 94%

Parallel expansion capability

Unlimited
N+1 redundancy capability Yes

Dimensions (H×W×D)

86.5(2U) ×

440(19″) ×

380 mm

131(3U) × 440(19″) × 520

mm

131(3U) × 443(19″) × 580

mm

Weight 7kg/12kg 11.7kg/26kg 11.7kg/28kg 23kg 25kg

Acoustic noise at 1m

≤45dBA ≤55dBA
Degree of protection against hazards and water ingress IP20

Mean Time Between Failures (MTBF)

100,000h

Environmental

Operating temperature

0°C to +40°C
Storage temperature -25°C to +55°C

Humidity

0 to 95% non-condensing
Altitude                                        at rated power

0.974 × rated power

0.920 × rated power

0.872 × rated power

0.820 × rated power

≤1500m

≤2000m

≤3000m

≤4000m

≤5000m

Input

Phases required

1Ph+N+PE
Rated voltage 230Vac

Voltage tolerance

100% load

70% load

50% load

 

±20%

-30% to +20%

-48% to +20%

Frequency range 35Hz to 70Hz

Power factor

≥0.99
THDi ≤3%

Bypass voltage range

max. voltage

min. voltage

 

230Vac +10%

230Vac -20% (optional -10%)

Output

Output phases available

1Ph+N+PE

Rated voltage

230Vac
Voltage regulation

double conversion mode

stored energy mode

 

±1%

±1%

Power factor

0.8 0.9
Frequency

double conversion mode

stored energy mode

 

50/60Hz ±10% (adj.)

50/60Hz ±0.1%

Crest factor

3:1
THD

linear load

nonlinear load

 

≤2%

≤3%

Transfer time

double conversion mode to stored energy mode

double conversion mode to bypass

 

0.00Sec

0.00Sec

Overload

double conversion mode

 

energy saving mode

 

105% up to 150%: 30S then transfer to bypass

>150%: transfer to bypass

 

up to110%: 60min

>110% up to 125%: 10min

>125% up to 150%: 1min

>150%: transfer to bypass

105% to 150%: 30S then cut off output

>150%: cut off output

40A breaker

(according to

breaker curve)

60A breaker

(according to

breaker curve)

Battery

Battery type

All types of lead acid and gel, sealed or vented

Normal voltage

24Vdc 72Vdc 192Vdc up to 240Vdc (selectable)

Max. charge current

6A 7A / 1A

Internal battery

‐ / 2x12Vx7or9 Ah ‐ / 6x12Vx7or9 Ah

Protections

Short circuit

Overload

Output overvoltage

Overheat

Battery low

Battery reverse (optional)

Self-diagnostics

EPO (optional)

Display

Audible & visual

Mains Failure, Low Battery, Overload, System Fault

Status LED & LCD

Double Conversion Mode, Energy Saving Mode, Low Battery,

Battery Test Failure, Overload, UPS Fault

LCD information

Input Voltage, Input Frequency, Output Voltage, Output Frequency,

Load Percentage, Battery Voltage, Parameters Set., History Record

Communication Interface

USB, RS485, Dry contacts (optional), SNMP card (optional), Relay card (optional), Parallel port

Features

  • 6, 10, 15 and 20 kVA UPS capacity
  • 3-Phase input, 1-Phase output
  • Double Conversion with capability for switching to Multi-Mode
  • (Automatically switches between Double Conversion and Line Interactive modes according to mains status if Multi-Mode is activated)
  • Intelligent controls with Digital Signal Processing (DSP)
  • Unlimited parallel expansion capability
  • 3-Level intelligent charging mode
  • Wide ranges of input voltage and input frequency
  • Excellent generator compatibility
  • Shared or separated batteries in parallel configuration (selectable)
  • Adjustable charging current
  • Advanced battery management
  • Intelligent monitoring function
  • Easy maintenance by providing optional MBB (Make Before Break) manual bypass
  • Optional Emergency Power Off function (EPO)

Technical Specifications

General

UPS Model CDT31-N06 CDT31-N10 CDT31-N15 CDT31-N20
Rated power 6kVA/5.4kW 10kVA/9kW 15kVA/12kW 20kVA/16kW

Applicable standard

IEC62040-3
UPS classification VFI SS CCC*

*C: 1 or 2 or 3 by order refer to IEC 62040-3

UPS topology

Double Conversion / Multi-Mode

(selectable by user)

Efficiency 94%

Parallel expansion capability

Up to 48 units
N+1 redundancy capability Yes

Dimensions (H×W×D)

443 × 131 × 580 mm 616 × 250 × 502 mm
Weight 23kg 25kg 45kg 46kg

Acoustic noise at 1m

≤55dBA ≤58dBA
Degree of protection against hazards and water ingress IP20

Mean Time Between Failures (MTBF)

100,000h

Environmental

Operating temperature

0°C to +40°C
Storage temperature -25°C to +55°C

Humidity

0 to 95% non-condensing
Altitude                                        at rated power

0.974 × rated power

0.920 × rated power

0.872 × rated power

0.820 × rated power

≤1500m

≤2000m

≤3000m

≤4000m

≤5000m

Input

Phases required

3Ph+N+PE
Rated voltage 400Vac

Voltage tolerance

100% load

70% load

50% load

 

±20%

-30% to +20%

-48% to +20%

Frequency range 35Hz to 70Hz

Power factor

≥0.99
THDi ≤3%

Bypass voltage range

max. voltage

min. voltage

 

230Vac +10%

230Vac -20% (optional -10%)

Output

Output phases available

1Ph+N+PE

Rated voltage

230Vac
Voltage regulation

double conversion mode

stored energy mode

 

±1%

±1%

Power factor

0.9 0.8
Frequency

double conversion mode

stored energy mode

 

50/60Hz ±10% (adj.)

50/60Hz ±0.1%

Crest factor

3:1
THD

linear load

nonlinear load

 

≤2%

≤3%

Transfer time

double conversion mode to stored energy mode

double conversion mode to bypass

 

0.00Sec

0.00Sec

Overload

double conversion mode

up to110%

>110% up to 125%

>125% up to 150%

>150%

 

energy saving mode

(according to breaker curve)

 

 

60min

10min

1min

transfer to bypass

40A breaker 60A breaker 100A breaker 125A breaker

Battery

Battery type

All types of lead acid and gel, sealed or vented

Normal voltage

192Vdc up to 240Vdc (selectable)

Max. charge current

6A 10A

Protections

Short circuit

Overload

Output overvoltage

Overheat

Battery low

Battery reverse (optional)

Self-diagnostics

EPO (optional)

Display

Audible & visual

Mains Failure, Low Battery, Overload, System Fault

Status LED & LCD

Double Conversion Mode, Energy Saving Mode, Low Battery,

Battery Test Failure, Overload, UPS Fault

LCD information

Input Voltage, Input Frequency, Output Voltage, Output Frequency,

Load Percentage, Battery Voltage, Parameters Set., History Record

Communication Interface

USB, RS485, Dry contacts (optional), SNMP card (optional), Relay card (optional), Parallel port

Features

  • 10, 15 and 20 kVA UPS capacity
  • Transformer based UPS
  • 3-Phase input, 1-Phase output
  • Double Conversion with capability for switching to Multi-Mode
  • (Automatically switches between Double Conversion and Line Interactive modes according to mains status if Multi-Mode is activated)
  • Intelligent controls with Digital Signal Processing (DSP)
  • Unlimited parallel expansion capability
  • 3-Level intelligent charging mode
  • Wide ranges of input voltage and input frequency
  • Excellent generator compatibility
  • Shared or separated batteries in parallel configuration (selectable)
  • Adjustable charging current
  • Advanced battery management
  • Intelligent monitoring function
  • Easy maintenance by providing optional MBB (Make Before Break) manual bypass
  • Optional Emergency Power Off function (EPO)

Technical Specifications

General

UPS Model CDT31-T10 CDT31-T15 CDT31-T20
Rated power 10kVA/8kW 15kVA/12kW 20kVA/16kW

Applicable standard

IEC62040-3
UPS classification VFI SS CCC*

*C: 1 or 2 or 3 by order refer to IEC 62040-3

UPS topology

Double Conversion / Multi-Mode

(selectable by user)

Efficiency 91%

Parallel expansion capability

Up to 48 units
N+1 redundancy capability Yes

Dimensions (H×W×D)

616 × 250 × 502 mm
Weight 93kg 121kg 145kg

Acoustic noise at 1m

≤58dBA
Degree of protection against hazards and water ingress IP20

Mean Time Between Failures (MTBF)

100,000h

Environmental

Operating temperature

0°C to +40°C
Storage temperature -25°C to +55°C

Humidity

0 to 95% non-condensing
Altitude                                        at rated power

0.974 × rated power

0.920 × rated power

0.872 × rated power

0.820 × rated power

≤1500m

≤2000m

≤3000m

≤4000m

≤5000m

Input

Phases required

3Ph+N+PE
Rated voltage 400Vac

Voltage tolerance

100% load

70% load

50% load

 

±20%

-30% to +20%

-48% to +20%

Frequency range 35Hz to 70Hz

Power factor

≥0.99
THDi ≤3%

Bypass voltage range

max. voltage

min. voltage

 

230Vac +10%

230Vac -20% (optional -10%)

Output

Output phases available

1Ph+N+PE

Rated voltage

230Vac
Voltage regulation

double conversion mode

stored energy mode

 

±1%

±1%

Power factor

0.8
Frequency

double conversion mode

stored energy mode

 

50/60Hz ±10% (adj.)

50/60Hz ±0.1%

Crest factor

3:1
THD

linear load

nonlinear load

 

≤2%

≤3%

Transfer time

double conversion mode to stored energy mode

double conversion mode to bypass

 

0.00Sec

0.00Sec

Overload

double conversion mode

up to110%

>110% up to 125%

>125% up to 150%

>150%

 

energy saving mode

(according to breaker curve)

 

 

60min

10min

1min

transfer to bypass

60A breaker 100A breaker 125A breaker

Isolation

Galvanic isolation from AC mains and DC link to AC output

Battery

Battery type

All types of lead acid and gel, sealed or vented

Normal voltage

192Vdc up to 240Vdc (selectable)

Max. charge current

10A

Protections

Short circuit

Overload

Output overvoltage

Overheat

Battery low

Battery reverse (optional)

Self-diagnostics

EPO (optional)

Display

Audible & visual

Mains Failure, Low Battery, Overload, System Fault

Status LED & LCD

Double Conversion Mode, Energy Saving Mode, Low Battery,

Battery Test Failure, Overload, UPS Fault

LCD information

Input Voltage, Input Frequency, Output Voltage, Output Frequency,

Load Percentage, Battery Voltage, Parameters Set., History Record

Communication Interface

USB, RS485, Dry contacts (optional), SNMP card (optional), Relay card (optional), Parallel port

Features

  • 10, 15, 20, 30 and 40 kVA UPS capacity
  • 3-Phase input, 3-Phase output
  • Ultra high efficiency up to 96% in Double Conversion mode / 99% in Line Interactive mode
  • Double Conversion with capability for switching to Multi-Mode
  • (Automatically switches between Double Conversion and Line Interactive modes according to mains status if Multi-Mode is activated)
  • Intelligent controls with Digital Signal Processing (DSP)
  • Unlimited parallel expansion capability
  • 3-Level intelligent charging mode
  • Wide ranges of input voltage and input frequency
  • Excellent generator compatibility
  • Shared or separated batteries in parallel configuration (selectable)
  • Adjustable charging current
  • Advanced battery management
  • Intelligent monitoring function
  • Easy maintenance by providing optional MBB (Make Before Break) manual bypass
  • Optional Emergency Power Off function (EPO)

Technical Specifications

General

UPS Model CDT33-N10 CDT33-N15 CDT33-N20 CDT33-N30 CDT33-N40
Rated power 10kVA/9kW 15kVA/13.5kW 20kVA/18kW 30kVA/27kW 40kVA/36kW

Applicable standard

IEC62040-3
UPS classification VFI SS CCC*

*C: 1 or 2 or 3 by order refer to IEC 62040-3

UPS topology

Double Conversion / Multi-Mode

(selectable by user)

Efficiency 94% 95% 96%

Parallel expansion capability

Up to 48 units
N+1 redundancy capability Yes

Dimensions (H×W×D)

870 × 250 × 830 mm
Weight 42kg 45kg 46kg 71kg 73kg

Acoustic noise at 1m

≤58dBA
Degree of protection against hazards and water ingress IP20

Mean Time Between Failures (MTBF)

100,000h

Environmental

Operating temperature

0°C to +40°C
Storage temperature -25°C to +55°C

Humidity

0 to 95% non-condensing
Altitude                                        at rated power

0.974 × rated power

0.920 × rated power

0.872 × rated power

0.820 × rated power

≤1500m

≤2000m

≤3000m

≤4000m

≤5000m

Input

Phases required

3Ph+N+PE
Rated voltage 400Vac

Voltage tolerance

100% load

70% load

50% load

 

±20%

-30% to +20%

-48% to +20%

Frequency range 35Hz to 70Hz

Power factor

≥0.99
THDi ≤3%

Bypass voltage range

max. voltage

min. voltage

 

400Vac +10%

400Vac -20% (optional -10%)

Output

Output phases available

3Ph+N+PE

Rated voltage

400Vac
Voltage regulation

double conversion mode

stored energy mode

 

±1%

±1%

Power factor

0.9
Frequency

double conversion mode

stored energy mode

 

50/60Hz ±10% (adj.)

50/60Hz ±0.1%

Crest factor

3:1
THD

linear load

nonlinear load

 

≤2%

≤3%

Transfer time

double conversion mode to stored energy mode

double conversion mode to bypass

 

0.00Sec

0.00Sec

Overload

double conversion mode

up to110%

>110% up to 125%

>125% up to 150%

>150%

 

energy saving mode

(according to breaker curve)

 

 

60min

10min

1min

transfer to bypass

20A breaker 32A breaker 40A breaker 63A breaker 80A breaker

Battery

Battery type

All types of lead acid and gel, sealed or vented

Normal voltage

192Vdc up to 240Vdc (selectable) 384Vdc up to

480Vdc (selectable)

Max. charge current

10A

Protections

Short circuit

Overload

Output overvoltage

Overheat

Battery low

Battery reverse (optional)

Self-diagnostics

EPO (optional)

Display

Audible & visual

Mains Failure, Low Battery, Overload, System Fault

Status LED & LCD

Double Conversion Mode, Energy Saving Mode, Low Battery,

Battery Test Failure, Overload, UPS Fault

LCD information

Input Voltage, Input Frequency, Output Voltage, Output Frequency,

Load Percentage, Battery Voltage, Parameters Set., History Record

Communication Interface

USB, RS485, Dry contacts (optional), SNMP card (optional), Relay card (optional), Parallel port

Features

  • 10, 15, 20, 30 and 40 kVA UPS capacity
  • Transformer based UPS
  • 3-Phase input, 3-Phase output
  • Double Conversion with capability for switching to Multi-Mode
  • (Automatically switches between Double Conversion and Line Interactive modes according to mains status if Multi-Mode is activated)
  • Intelligent controls with Digital Signal Processing (DSP)
  • Unlimited parallel expansion capability
  • 3-Level intelligent charging mode
  • Wide ranges of input voltage and input frequency
  • Excellent generator compatibility
  • Shared or separated batteries in parallel configuration (selectable)
  • Adjustable charging current
  • Advanced battery management
  • Intelligent monitoring function
  • Easy maintenance by providing optional MBB (Make Before Break) manual bypass
  • Optional Emergency Power Off function (EPO)

Technical Specifications

General

UPS Model CDT33-T10 CDT33-T15 CDT33-T20 CDT33-T30 CDT33-T40
Rated power 10kVA/9kW 15kVA/13.5kW 20kVA/18kW 30kVA/27kW 40kVA/36kW

Applicable standard

IEC62040-3
UPS classification VFI SS CCC*

*C: 1 or 2 or 3 by order refer to IEC 62040-3

UPS topology

Double Conversion / Multi-Mode

(selectable by user)

Efficiency 91% 92% 93%

Parallel expansion capability

Up to 48 units
N+1 redundancy capability Yes

Dimensions (H×W×D)

870 × 250 × 830 mm
Weight 96kg 123kg 146kg 214kg 253kg

Acoustic noise at 1m

≤58dBA
Degree of protection against hazards and water ingress IP20

Mean Time Between Failures (MTBF)

100,000h

Environmental

Operating temperature

0°C to +40°C
Storage temperature -25°C to +55°C

Humidity

0 to 95% non-condensing
Altitude                                        at rated power

0.974 × rated power

0.920 × rated power

0.872 × rated power

0.820 × rated power

≤1500m

≤2000m

≤3000m

≤4000m

≤5000m

Input

Phases required

3Ph+N+PE
Rated voltage 400Vac

Voltage tolerance

100% load

70% load

50% load

 

±20%

-30% to +20%

-48% to +20%

Frequency range 35Hz to 70Hz

Power factor

≥0.99
THDi ≤3%

Bypass voltage range

max. voltage

min. voltage

 

400Vac +10%

400Vac -20% (optional -10%)

Output

Output phases available

3Ph+N+PE

Rated voltage

400Vac
Voltage regulation

double conversion mode

stored energy mode

 

±1%

±1%

Power factor

0.9
Frequency

double conversion mode

stored energy mode

 

50/60Hz ±10% (adj.)

50/60Hz ±0.1%

Crest factor

3:1
THD

linear load

nonlinear load

 

≤2%

≤3%

Transfer time

double conversion mode to stored energy mode

double conversion mode to bypass

 

0.00Sec

0.00Sec

Overload

double conversion mode

up to110%

>110% up to 125%

>125% up to 150%

>150%

 

energy saving mode

(according to breaker curve)

 

 

60min

10min

1min

transfer to bypass

20A breaker 32A breaker 40A breaker 63A breaker 80A breaker

Isolation

Galvanic isolation from AC mains and DC link to AC output

Battery

Battery type

All types of lead acid and gel, sealed or vented

Normal voltage

192Vdc up to 240Vdc (selectable) 384Vdc up to

480Vdc (selectable)

Max. charge current

10A

Protections

Short circuit

Overload

Output overvoltage

Overheat

Battery low

Battery reverse (optional)

Self-diagnostics

EPO (optional)

Display

Audible & visual

Mains Failure, Low Battery, Overload, System Fault

Status LED & LCD

Double Conversion Mode, Energy Saving Mode, Low Battery,

Battery Test Failure, Overload, UPS Fault

LCD information

Input Voltage, Input Frequency, Output Voltage, Output Frequency,

Load Percentage, Battery Voltage, Parameters Set., History Record

Communication Interface

USB, RS485, Dry contacts (optional), SNMP card (optional), Relay card (optional), Parallel port