CDR11-N Series UPS
- 1, 2, 3, 6 and 10 kVA UPS capacity
- Rack mount UPS
- Designed for 19” standard rack with 2 units height for 1kVA UPS and 3 units height for others
- Internal battery capability for 1,2 and 3kVA UPS
- 1-Phase input, 1-Phase output
- Double Conversion with capability for switching to Multi-Mode
- (Automatically switches between Double Conversion and Line Interactive modes according to mains status if Multi-Mode is activated)
- Intelligent controls with Digital Signal Processing (DSP)
- Unlimited parallel expansion capability for 6 and 10 kVA UPS
- 3-Level intelligent charging mode
- Wide ranges of input voltage and input frequency
- Excellent generator compatibility
- Shared or separated batteries in parallel configuration (selectable)
- Adjustable charging current
- Advanced battery management
- Intelligent monitoring function
- Easy maintenance by providing optional MBB (Make Before Break) manual bypass
- Optional Emergency Power Off function (EPO)
CDR11-N Series UPS Technical Specifications
General |
|||||
UPS Model | CDR11‐N01/
CDR11‐N01i |
CDR11‐N02/
CDR11‐N02i |
CDR11‐N03/
CDR11‐N03i |
CDR11‐N06 | CDR11‐N10 |
Rated power | 1kVA/0.8kW | 2kVA/1.6kW | 3kVA/2.4kW | 6kVA/5.4kW | 10kVA/9kW |
Applicable standard |
IEC62040-3 | ||||
UPS classification | VFI SS CCC*
*C: 1 or 2 or 3 by order refer to IEC 62040-3 |
||||
UPS topology |
Double Conversion / Multi-Mode
(selectable by user) |
||||
Efficiency | 87% | 89% | 94% | ||
Parallel expansion capability |
‐ | Unlimited | |||
N+1 redundancy capability | Yes | ||||
Dimensions (H×W×D) |
86.5(2U) ×
440(19″) × 380 mm |
131(3U) × 440(19″) × 520
mm |
131(3U) × 443(19″) × 580
mm |
||
Weight | 7kg/12kg | 11.7kg/26kg | 11.7kg/28kg | 23kg | 25kg |
Acoustic noise at 1m |
≤45dBA | ≤55dBA | |||
Degree of protection against hazards and water ingress | IP20 | ||||
Mean Time Between Failures (MTBF) |
100,000h | ||||
Environmental |
|||||
Operating temperature |
0°C to +40°C | ||||
Storage temperature | -25°C to +55°C | ||||
Humidity |
0 to 95% non-condensing | ||||
Altitude at rated power
0.974 × rated power 0.920 × rated power 0.872 × rated power 0.820 × rated power |
≤1500m
≤2000m ≤3000m ≤4000m ≤5000m |
||||
Input |
|||||
Phases required |
1Ph+N+PE | ||||
Rated voltage | 230Vac | ||||
Voltage tolerance 100% load 70% load 50% load |
±20% -30% to +20% -48% to +20% |
||||
Frequency range | 35Hz to 70Hz | ||||
Power factor |
≥0.99 | ||||
THDi | ≤3% | ||||
Bypass voltage range max. voltage min. voltage |
230Vac +10% 230Vac -20% (optional -10%) |
||||
Output |
|||||
Output phases available |
1Ph+N+PE | ||||
Rated voltage |
230Vac | ||||
Voltage regulation
double conversion mode stored energy mode |
±1% ±1% |
||||
Power factor |
0.8 | 0.9 | |||
Frequency
double conversion mode stored energy mode |
50/60Hz ±10% (adj.) 50/60Hz ±0.1% |
||||
Crest factor |
3:1 | ||||
THD
linear load nonlinear load |
≤2% ≤3% |
||||
Transfer time double conversion mode to stored energy mode double conversion mode to bypass |
0.00Sec 0.00Sec |
||||
Overload
double conversion mode
energy saving mode |
105% up to 150%: 30S then transfer to bypass >150%: transfer to bypass |
up to110%: 60min >110% up to 125%: 10min >125% up to 150%: 1min >150%: transfer to bypass |
|||
105% to 150%: 30S then cut off output
>150%: cut off output |
40A breaker
(according to breaker curve) |
60A breaker
(according to breaker curve) |
|||
Battery |
|||||
Battery type |
All types of lead acid and gel, sealed or vented | ||||
Normal voltage |
24Vdc | 72Vdc | 192Vdc up to 240Vdc (selectable) | ||
Max. charge current |
6A | 7A / 1A | |||
Internal battery |
‐ / 2x12Vx7or9 Ah | ‐ / 6x12Vx7or9 Ah | ‐ | ||
Protections |
|||||
Short circuit |
|||||
Overload |
|||||
Output overvoltage |
|||||
Overheat |
|||||
Battery low |
|||||
Battery reverse (optional) |
|||||
Self-diagnostics |
|||||
EPO (optional) |
|||||
Display |
|||||
Audible & visual |
Mains Failure, Low Battery, Overload, System Fault | ||||
Status LED & LCD |
Double Conversion Mode, Energy Saving Mode, Low Battery,
Battery Test Failure, Overload, UPS Fault |
||||
LCD information |
Input Voltage, Input Frequency, Output Voltage, Output Frequency,
Load Percentage, Battery Voltage, Parameters Set., History Record |
||||
Communication Interface |
|||||
USB, RS485, Dry contacts (optional), SNMP card (optional), Relay card (optional), Parallel port |
CDR31-N Series UPS
- 6 and 10 kVA UPS capacity
- Rack mount UPS
- Designed for 19” standard rack with 3 units height
- 3-Phase input, 1-Phase output
- Double Conversion with capability for switching to Multi-Mode
- (Automatically switches between Double Conversion and Line Interactive modes according to mains status if Multi-Mode is activated)
- Intelligent controls with Digital Signal Processing (DSP)
- Unlimited parallel expansion capability
- 3-Level intelligent charging mode
- Wide ranges of input voltage and input frequency
- Excellent generator compatibility
- Shared or separated batteries in parallel configuration (selectable)
- Adjustable charging current
- Advanced battery management
- Intelligent monitoring function
- Easy maintenance by providing optional MBB (Make Before Break) manual bypass
- Optional Emergency Power Off function (EPO)
CDR31-N Series UPS Technical Specifications
General |
||
UPS Model | CDR31-N6 | CDR31-N10 |
Rated power | 6kVA/5.4kW | 10kVA/9kW |
Applicable standard |
IEC62040-3 | |
UPS classification | VFI SS CCC*
*C: 1 or 2 or 3 by order refer to IEC 62040-3 |
|
UPS topology |
Double Conversion / Multi-Mode
(selectable by user) |
|
Efficiency | 94% | |
Parallel expansion capability |
Up to 48 units | |
N+1 redundancy capability | Yes | |
Dimensions (H×W×D) |
131(3U) × 443(19″) × 580 mm | |
Weight | 23kg | 25kg |
Acoustic noise at 1m |
≤55dBA | |
Degree of protection against hazards and water ingress | IP20 | |
Mean Time Between Failures (MTBF) |
100,000h | |
Environmental |
||
Operating temperature |
0°C to +40°C | |
Storage temperature | -25°C to +55°C | |
Humidity |
0 to 95% non-condensing | |
Altitude at rated power
0.974 × rated power 0.920 × rated power 0.872 × rated power 0.820 × rated power |
≤1500m
≤2000m ≤3000m ≤4000m ≤5000m |
|
Input |
||
Phases required |
3Ph+N+PE | |
Rated voltage | 400Vac | |
Voltage tolerance 100% load 70% load 50% load |
±20% -30% to +20% -48% to +20% |
|
Frequency range | 35Hz to 70Hz | |
Power factor |
≥0.99 | |
THDi | ≤3% | |
Bypass voltage range max. voltage min. voltage |
230Vac +10% 230Vac -20% (optional -10%) |
|
Output |
||
Output phases available |
1Ph+N+PE | |
Rated voltage |
230Vac | |
Voltage regulation
double conversion mode stored energy mode |
±1% ±1% |
|
Power factor |
0.9 | |
Frequency
double conversion mode stored energy mode |
50/60Hz ±10% (adj.) 50/60Hz ±0.1% |
|
Crest factor |
3:1 | |
THD
linear load nonlinear load |
≤2% ≤3% |
|
Transfer time double conversion mode to stored energy mode double conversion mode to bypass |
0.00Sec 0.00Sec |
|
Overload
double conversion mode up to110% >110% up to 125% >125% up to 150% >150%
energy saving mode (according to breaker curve) |
60min 10min 1min transfer to bypass |
|
40A breaker | 60A breaker | |
Battery |
||
Battery type |
All types of lead acid and gel, sealed or vented | |
Normal voltage |
192Vdc up to 240Vdc (selectable) | |
Max. charge current |
6A | |
Protections |
||
Short circuit |
||
Overload |
||
Output overvoltage |
||
Overheat |
||
Battery low |
||
Battery reverse (optional) |
||
Self-diagnostics |
||
EPO (optional) |
||
Display |
||
Audible & visual |
Mains Failure, Low Battery, Overload, System Fault | |
Status LED & LCD |
Double Conversion Mode, Energy Saving Mode, Low Battery,
Battery Test Failure, Overload, UPS Fault |
|
LCD information |
Input Voltage, Input Frequency, Output Voltage, Output Frequency,
Load Percentage, Battery Voltage, Parameters Set., History Record |
|
Communication Interface |
||
USB, RS485, Dry contacts (optional), SNMP card (optional), Relay card (optional), Parallel port |